Traps, Interceptors & Storm Drainage
PlumberPractice study guide with diagrams.
Traps, Interceptors & Storm Drainage
Learning Objectives
By the end of this chapter, you should be able to:
1.1 Fundamentals of Trap Seal Protection
A trap is a fitting or device that maintains a water seal against sewer gas entry. The trap seal is the vertical distance between the trap's crown weir and the dip (bottom of the internal curve). The IPC requires that every trap have a minimum seal of 2 inches and a maximum seal of 4 inches (except where a deeper seal is specifically required for a particular fixture). Traps with seals deeper than 4 inches are prohibited because they increase the risk of self-siphonage and clogging.
Key points:
Trap types commonly seen in the field:
Prohibited traps include: traps with moving parts, traps that depend on interior partitions, and bell traps (often found in old floor drains).
1.2 Trap Materials and Joints
Traps must be made of materials listed for use in drainage systems: cast iron, galvanized steel, copper or copper alloy, brass, PVC, ABS, or other approved materials. The material must match the piping system to which it is connected, or be joined with approved transition fittings.
Inspection point: Check that the trap is not chrome-plated brass in a concealed location unless approved. Chrome traps are only for exposed applications.
Slip joints (mechanical joints) are permitted only on the trap inlet and outlet connections for fixtures such as sinks and lavatories. They are not allowed in concealed locations. A slip joint nut must be accessible.
1.3 Interceptors and Separators
Interceptors and separators are devices installed to prevent harmful, hazardous, or undesirable materials from entering the public sewer or drainage system. The IPC requires their use where the nature of the discharge warrants it.
Common types:
Installation requirements:
Sizing note: The code does not provide a single sizing table for grease interceptors. Instead, sizing is based on the drainage fixture unit (dfu) load and the flow rate of the fixtures served. The interceptor must be sized to handle the peak flow without allowing grease to escape. In practice, many jurisdictions require a minimum capacity (e.g., 20 gallons per minute) for commercial food service.
1.4 Backwater Valves
A backwater valve is a device installed on the building drain or sewer to prevent reverse flow (backflow) of sewage from the public sewer into the building. The IPC requires backwater valves where the lowest fixture is below the elevation of the next upstream manhole or sewer cover.
Key requirements:
Inspection point: Verify the valve is not installed in a location where it can be accidentally covered by concrete or flooring without an access panel.
1.5 Storm Drainage: Scope and Definitions
Storm drainage systems collect and convey rainwater, surface water, and groundwater away from the building. The IPC covers:
Important definitions:
Prohibition: Storm water must not be discharged into a sanitary sewer unless the jurisdiction specifically allows combined sewers. In most cases, storm and sanitary systems must be separate.
1.6 Roof Drainage and Sizing
Roof drains must be placed at the lowest points of the roof, and the roof must be sloped to drain. The IPC provides a sizing table (Table 1106.2) based on the rainfall rate (inches per hour) and the roof area (square feet). The table gives the required diameter of the roof drain and conductor for a given flow.
Sizing steps:
Example: For a 2-inch per hour rainfall rate, a 4-inch roof drain can serve approximately 1,800 square feet of roof area. For a 4-inch per hour rate, the same drain serves only about 900 square feet.
Inspection point: Check that the roof drain has a strainer or dome that prevents debris entry. The strainer must have an open area at least equal to the pipe area.
1.7 Conductors and Building Storm Drains
Vertical conductors must be sized according to the same table as roof drains. Horizontal storm drains must be sized based on the slope and the dfu load or the hydraulic flow. The IPC provides a separate table for horizontal storm drain sizing (Table 1106.3) based on slope.
Minimum slopes for horizontal storm drains:
Cleanouts are required on storm drains at intervals not exceeding 100 feet, and at changes in direction greater than 45 degrees.
Venting: Storm drains are not required to be vented unless they contain traps (e.g., a floor drain in a parking garage that connects to the storm system). If a trap is used, it must be vented.
1.8 Combined Sanitary and Storm Systems
In some older municipalities, a combined sewer carries both sanitary and storm water. The IPC allows this only if the jurisdiction permits it. In new construction, separate systems are the standard. If a combined system is allowed, the sanitary and storm loads must be added together for sizing.
1.9 Subsurface and Groundwater Drainage
The IPC also covers foundation drainage and sump pumps:
Inspection point: Verify that the sump pump discharge has a check valve to prevent backflow into the pit.
1.10 Code Navigation: Where to Find It
For an open-book exam, knowing where to look is half the battle. Use this quick reference:
| Topic | IPC Section |
|---|---|
| Trap seal requirements (2–4 inches) | Section 1002.1 |
| Trap distance from fixture (24 inches) | Section 1002.2 |
| Prohibited traps | Section 1002.3 |
| Trap materials and joints | Section 1002.4 |
| Interceptors and separators (general) | Section 1003.1 |
| Grease interceptor sizing | Section 1003.3 |
| Backwater valves | Section 1102.5 |
| Storm drainage scope | Chapter 11 (general) |
| Roof drain sizing table | Table 1106.2 |
| Horizontal storm drain sizing | Table 1106.3 |
| Cleanouts on storm drains | Section 1105.1 |
| Sump pumps and ejectors | Section 1110 |
| Rainfall rate data | Appendix B (informative) |
Note: Appendix B is not part of the code text but is often used for design rainfall rates. Check if your jurisdiction adopts it.
1.11 Practical Inspection Points
When performing a code inspection on traps, interceptors, and storm drainage, the inspector typically verifies the following:
1.12 Common Code Violations to Avoid
Summary
This chapter covered the core requirements for traps, interceptors, and storm drainage systems. In the exam, you will be asked to apply these rules to practical scenarios. Remember that the IPC is a performance-based code: it sets minimum standards, and you must be able to find the exact section quickly. Practice navigating the code by looking up each section listed in the Code Navigation table above. On exam day, your code book is your best tool—use it early and often.
Final tip: For any question about sizing, always check the tables first. The IPC tables are the definitive source for pipe sizes, slopes, and capacities. Do not rely on memory for numbers; rely on your ability to find them.
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free